Ecol tests: Dissolved Gas Analysis (DGA)

  • • Standards: PN-EN 60567:2012
  • • Unit: ppm
  • • Oil quantity: 50 ml
  • • Application: electro-insulating liquids


  • method description:

    Testing using gas chromatography (GC) with flame ionisation detection (FID) and thermal conductivity detection (TCD). Using headspace extraction, the gas phase is extracted from the oil sample and analysed chromatographically.



    interpretation of results:

    Defects that occur in the transformer (e.g. overheating or discharge) cause the chemical bonds between the atoms that make up the hydrocarbon molecules to break. Depending on the type of defect that occurs in the transformer, different gases are generated. Based on the type of gases present in an oil sample, their content and mutual ratios and increments, it is possible to diagnose the type of fault present in a transformer and its activity.